Outdoor Pedestrian View of the Bayers Lake Community Outpatient Centre

We’re excited to be part of the team, led by EllisDon Infrastructure Healthcare (EDIH), that will build the new Bayers Lake Community Outpatient Centre in Nova Scotia. HH Angus’ Health Division will be providing mechanical consulting engineering services, working with Dillon Consulting in Halifax. This is the first P3 healthcare project in Nova Scotia, and will be an important facility for both the community and the entire province. According to Kim Spencer, HH Angus Health Division Director, “we’re very pleased to be able to support this new facility with HH Angus’ deep experience in the P3 delivery model, and proven track record in thoughtful healthcare design.”

The 134,000 ft2 Outpatient Centre will built on a 15-acre site in Halifax’s Bayers Lake Business Park. Planned services include primary care; clinics such as physio and occupational therapy; high blood pressure, diabetes and orthopedic assessment; 17 examination rooms; 24 dialysis stations; diagnostic imaging (x-rays and ultrasounds); blood collection; and post-surgery or post-treatment follow-up appointments.

Image courtesy of EDIH

High-resistance grounding provides safer, more reliable electrical distribution for healthcare facilities

High-resistance grounding is relatively simple and easy to apply in radial distribution systems. It has been used in the healthcare industry for many years, considered to be “best practice” for hospitals. The concept is well-known, recognized by the Canadian Electrical Code, and driven by four basic factors: power is not interrupted in the event of a single ground fault; negligible damage at the point of fault, resulting in lower repair costs and faster return of equipment to service; negligible arc flash hazard in the event of a single ground fault; and negligible risk of a single ground fault escalating into a damaging line to line or three phase fault.

It is best practice to have the low voltage (600V) and high voltage (4,160V) systems equipped with high-resistance grounding. This has often taken the form of a neutral  grounding resistor applied between transformer neutral and ground. An alarm is raised on the occurrence of a ground fault in the distribution as required by the installation codes. In modern relays, the zero-sequence sensor signal causes a pick up; then the simultaneous presence of unbalanced voltage to ground is verified before an alarm is indicated. To avoid the possibility of nuisance alarms caused by inrush currents and non-inear loads, the zero-sequence current sensor output is filtered and only the fundamental signal is extracted. These measures have been effective in avoiding nuisance alarms and trips in sensitive ground fault relays.

The primary benefit of using high-resistance grounding is the faulted feeder does not need to be isolated on the occurrence of a phase to ground fault.

Vantage Point

The use of high-resistance grounding offers many benefits.

Arc flash and blast hazard for a line to ground fault is prevented. For systems up to 4,160V, where the resistor let-through current is 10A (amperage) or less, the arc blast is unlikely. Such systems can continue to operate with one ground fault. The fault does not escalate so the distribution system is safer. Accidents causing line to ground faults will not produce a hazardous blast or arc flash.

Fault damage at the point of fault is very low and can be easily repaired. It minimizes maintenance repair costs. Motor and generator laminations will not get burnt and winding repair costs will be small.

For systems up to 4,160V, where the resistor let-through current is 10A or less, the line to ground fault can be kept on the system continuously. No fault isolation needs to occur per Canadian Electrical Code 10-1100 through 1108.

Damaging voltage transients that can occur on ungrounded systems are avoided since the system is grounded.

On the other hand, four application concerns arise when resistance grounding is applied to distribution.

All cables need to have a line to ground voltage rating of line to line voltage for the maximum duration of the line to ground fault. This is not an issue at low voltage, such as 600V. The standard cables have adequate ratings.

Lightning arrestors and surge suppression devices that are connected line to ground also need to be adequately rated.

Voltage to ground impressed on capacitors will also increase to line to line value.

The circuit breakers and contractors employed in resistance grounded systems must be able to break L-L voltage across one pole of the device. For example, a three pole 600V breaker must be able to open fault current and withstand 600V across one pole, which most 600V breakers are capable of. However, some breakers only have a 347/600V rating. This  means they are able to interrupt only 347V across one pole, making them unsuitable. The same would apply to contractors.

In this scenario, a ground fault occurs in the switchboard downstream of a transfer switch.

Fault Scenario

In a typical hospital, there will be a 600V normal power system and a 600V generator power system. The most critical loads are fed from the emergency power distribution, which is downstream of one or more transfer switches. The transfer switches get power from both the normal power system and the generator power system. In this scenario, a ground fault occurs in the switchboard downstream of a transfer switch. This fault could have a number of causes.

In the solidly grounded system, the ground fault results in a large current flow creating significant damage within the switchboard, vapourizing components and coating the inside of the switchboard with semiconductive residue. The high fault current subjects the upstream transformer to high stresses and causes the upstream breaker to trip. All power to the critical loads is lost. The loss of power is sensed at the transfer switch, which starts the emergency generator and transfers the critical load over to the generator. Since the switchboard is contaminated with residue from the previous fault, another fault occurs and this further damages the switchboard. It also stresses the generator with a high magnitude fault current and causes the generator breaker for the transfer switch to trip. The critical loads, including the emergency department and intensive care unit, are shut down and remain so until their feeders can be cut away from the failed switchboard, spliced and extended to another source of power – a process that takes many hours and leaves the critical loads on normal power only. The hospital is forced into emergency mode and must transfer critical patients to other areas of the hospital, which were not designed for their care, and in some  cases to another hospital. Full restoration of the system requires replacement of the switchboard. This takes many months as switchgear is built to order.

In the resistance grounded system, the ground fault results in an alarm. There are no power interruptions, the main transformer is not subjected to the stresses of a fault, and the generator does not start, and is not exposed to a fault current. Most importantly, the damage to the switchboard is minimal, requiring the replacement of a single insulator, which is scheduled for a time when the hospital can accommodate the short shutdown necessary to perform the work.

Ground Current Detection

A major functional enhancement occurs when detection and alarm of ground faults is supplemented with monitoring of all the feeders to indicate which feeder is faulted and administer assistance for quickly locating the fault.

To provide assistance in locating a fault in highresistance grounded systems, the fault current is modulated by oscillating it between values such as 5A-10A, typically at one cycle per second. This is accomplished by changing the resistor value using a contactor, which has been called ‘pulsing’ in the industry. The  pulsing is manually started. A flexible zero-sequence sensor or a clamp on the current transformer encircling all phase conductors is used to provide an oscillating signal to a handheld multimeter. Readings are taken on the faulted feeder moving away from the switchboard. The signal will disappear once the fault location is passed. Often, two or three measurements are sufficient to point to the fault location. Readings are taken from the outside of the grounded raceways, conduits or busways, while the system is energized and running. This technique has been in use for many years. It is quite effective for voltages up to 4,160V.

Tripping Up

The primary benefit of using high-resistance grounding is the faulted feeder does not need to be isolated on the occurrence of a phase to ground fault. While the faulted system continues to operate, there is a possibility that another phase to ground fault may occur on a different phase in some other weak spot in the distribution system. With the presence of a second fault, the fault current is no longer limited by the resistor and will be a higher magnitude fault. The zero-sequence sensors continue to monitor the fault current and if a significantly higher current than that limited by the resistor is detected, then the system recognizes that a line to ground to line fault  exists and identifies the two feeders involved. Only one feeder breaker needs to be tripped to revert the rest of the system to a single fault condition. A level of priority can be assigned based on the relative importance of the feeders. The one feeder with lower priority is tripped. Fast operation provides protection and minimizes fault damage. Such systems have been in use for a long time and this first fault alarm and second fault trip is best applied to monitor specific loads.

Improving the System

On low voltage systems and systems up to 5 kilovolt (kV), high-resistance grounding  provides a safer and more reliable distribution system. The arc flash hazard in the event of a line to ground fault can be eliminated and power continuity maintained. The  performance of the distribution system can be enhanced by using high reliability neutral grounding resistors with low temperature coefficients, monitoring the neutral ground resistor continuously, using a pulsing system to find ground faults and using coordinated selective second fault tripping. In many applications, it is more beneficial to apply the neutral grounding resistor at the main bus. In such a case, the incoming supply feeders can be monitored for ground fault very cost-effectively by applying multi-circuit relays.

Authors

Ajit Bapat, P.Eng., Owner of Power Solutions
Nick Carter, P.Eng., Principal at HH Angus & Associates Ltd.
Sergio Panetta, P.Eng., Vice-president of engineering at I-Gard Corp.